Restrictions inside the unit
Start closest to the symptom. Strainers fill with magnetite and construction debris and are the first thing we check. Plate heat exchangers foul with scale on the DHW side, narrowing the channels. Control valves seize part-open, and differential pressure control valves set too far closed strangle the unit deliberately. Each one is measurable, and each one is far cheaper to correct than replacing the HIU.
- Blocked primary and secondary strainers
- Scaled DHW plate heat exchanger
- Control valve stuck part-open
- DPCV set too low for the unit duty