Common pressurisation unit faults
The alarms tell you the symptom; the cause is usually elsewhere. A low pressure alarm means the system is losing water — a leak, a passing safety valve, or a failed expansion vessel allowing pressure to swing and discharge. A high pressure alarm often means the fill solenoid is passing or the expansion vessel is waterlogged so there is nowhere for the expanded volume to go. A unit that runs continuously has either a genuine leak to find or a non-return valve letting system water back into the break tank.
- Low pressure alarms and system water loss
- High pressure alarms and safety valve discharge
- Passing fill solenoids and non-return valves
- Failed pressure sensors and controllers
- Pump failure on single and twin pump units
- Break tank float valve and level switch faults